HCC - AC Wiring

Connecting the controller to primary AC power should be done by a licensed electrician following all local codes. Install in approved conduit and fittings. The controller can operate with either 120VAC or 230VAC power. Supply wires must be 14AWG/ 2 mm2 or larger.

  1. Turn AC power "off" at the source, and verify that it is off.

  2. Disconnect the "facepack" ribbon cable.

  3. Remove the "facepack."
  4. Remove the "cover" from the junction box.
  5. Strip about 0.5” (13 mm) of insulation from the end of each AC power wire.

  6. Route the wires through the "conduit opening" inside the junction box.
  7. Connect AC wiring using supplied terminal block (or taped wire nuts where permissible).
 
     support_icc2_wiring_1.jpg

 

 
     support_icc2_wiring_2.jpg

 

 
     support_icc2_wiring_3.jpg

 

Wiring Block 
     support_icc2_wiring_4.jpg

 

Wiring Block 
     icc2_support_earth_ground5.jpg
  1. Insert copper wire from earth ground hardware, and tighten screw in front.
  2. Minimum 10 AWG/5mm2 wire to earth ground hardware.
  3. Add copper-clad steel ground rods and/or plates sufficient to achieve 10Ω or less resistance at a minimum 8’/2.5 m away from controller.